Panasonic MCB brings across high quality and safety, contributing its best expertise for the Indian electricity distribution, securing lives and electrical installations.
Type | B | C | D |
Magnetic Release Setting | (3-5) In | (5-10) In | (10-20) In |
No. of Poles (Execution) | SP | SP, SP+N, DP, TP, TP+N, FP | SP, DP, TP, FP |
Rated Current (In) A | 6A to 63A | ||
Rated Voltage (Ue) V~ | SP, TP+N: AC 240V/415V, SP+N: AC 240V, DP,TP,FP: AC 415V | ||
Rated Frequency (f) Hz | 50Hz | ||
Rated Short Circuit Breaking Capacity | 1000 A | ||
Serive Short Circuit Breaking Capacity | 7500 A | ||
Energy Limitation | Class 3 | ||
Tripping Mechanism | Thermal & Magnetic Type | ||
Normal Ambient Temparature | 30oC | ||
Power Loss | Much less than standard values | ||
Rated Impulse Voltage | 4kV | ||
Dielectric Strength | 2000V 1min | ||
Protection Class | IP20 | ||
Mounting | On DIN Rail (35mm x 7.5mm) | ||
Connections | 1 sq.mm to 25 sq.mm for Cu conductors |
Panasonic MCB is having Three Level Indications to identify clear ON, OFF, and TRIP POSITION. The Trip Position helps user to identify the fault ciruit.
This is a mechanism of a Breaker that, compared to a General Breaker, cuts off the current several times faster (High Speed) while suppressing the large current (current limiting) in respect to a large current (short circuit current) when a short circuit accident occurs.
Minimum let through energy in case of fault; ensures safety and longetivity of downstream circuit/installation.
Rated Short-circuit capacity (A) |
Energy Limiting Classes | ||
1 I2t max(A2s) | 2 I2t max(A2s) | 3 I2t max(A2s) | |
B-type C-type | B-type C-type | B-type C-type | |
1000 | limit specified | 310000 370000 | 90000 110000 |
The handle and the contact move independently in order to create a firm and instantaneous contact when connecting together.
Wiping contact design ensures the proper current flow with continuity, while contact makes on condition, to prevent no contact defect.
Fully insulated safety shutters provide safety in connection. During wiring, they guide the cable towards the terminal clamp and the shutter gives total protection.
Customer have the choice of using either a bus bar or cable to make connections on both sides thus providing the ultimate flexibility.
The surface of MCB has been designed in such a way that it does not allow dust to settle on its surface. The MCB thus retains it's new look for years.